T-DRILL Industries Inc.
1740 Corporate Drive, #820
Norcross, GA 30093, USA
Tel. (+1) 770-925-0520
Toll free. (+1) 800-554-2730
Fax. (+1) 770-925-3912

 
 
 
Home
Engineer
Process
Codes & Standards
RSMeans
Training
Specification
Radius Thicken
Burst Pressure
Braze vs. Solder
 

Specification

 

ASME B31.9 2004
BUILDING SERVICES PIPING

Section 930.2 Mechanically Formed Extruded Outlets in Copper Tube
(a) Mechanically formed extruded outlets shall be perpendicular to the axis of the run tube (header). They shall be formed by drilling a pilot hole and drawing out the tube surface to form a collar having a height of not less than three times the thickness of the branch wall.
(b) The inner branch tube end shall conform to the shape of the inner curve of the run tube. Insertion of the branch tube shall be controlled to assure alignment with specified depth into the collar without extending into the flow stream so as to provide internal reinforcement to the collar.
(c) Branches can be formed up to the run tube size as shown in ASTM F 2014. Forming procedures shall be in accordance with the tool manufacturer’s recommendations.
(d) All joints shall be brazed in accordance with para. 928.1

(e) The allowable pressure for the joint shall be the lowest value calculated by Eqs. (10), (11), or (12).

Click Below to download in Word format

ASME B31.9

 
 